LIST
OF STANDARD FEATURES and MINIMUM SPECIFICATIONS
|
| CONFIGURED
AS A HAZARDOUS MATERIAL STORAGE BUILDING(s)
|
|
CLASSIFICATION:
H2 Occupancy.
SECONDARY
CONTAINMENT:
Minimum of 25% designed storage capacity
in liquids.
CODE
COMPLIANCE:
Meet or exceed latest edition of applicable
UBC, SBC, BOCA National Building Codes;
NFPA, UFC, EPA, NEC, OSHA codes and
regulation with respect to compliance
in design.
MATERIALS
and
WORKMANSHIP:
Meets or exceeds all applicable ANSI,
AWS, AISC, US Product, ASTM standards
regarding materials and workmanship.
FEDERAL
CONTRACT AVAILABILITY:
GSA
Contract Number: GS-28F-8056H
DLA
Contract Number: SPO500-98-D-9010.
QUALITY
ASSURANCE:
Engineering, production capability,
testing and inspection program approved
by a Nationally Recognized Testing
Laboratory (NRTL).
APPROVAL:
3rd Party Listed - Warnock Hersey
listed, all standard models.
|
|
|
CONSTRUCTION:
All welded steel structural support and sump;
Fire-rated buildings use UL two (2) or four
(4) Hour Fire-rated design construction for
walls, sump walls and ceiling/roof; Non-Fire-rated
buildings use welded steel construction. |
| . |
|
MINIMUM LOADS
|
- WIND
110 MPH (EXP. C);
- ROOF
40 PSF, I60 UPLIFT;
- SEISMIC
BRACING, ZONE 4;
- FLOOR
250 PSF;
- INTERNAL
PRESSURE 100 PSF;
- EXPLOSION
VENTING 20 PSF. (EXPLOSION RELIEF BUILDINGS
ONLY)
|
| ELECTRICAL:
Approved electrical components are factory
installed in accord with manufacturer's directions
and wired in accord with the most current
National Electric Code. Interior wiring complies
with requirements for a Group C or D hazardous
material environment, and exterior wiring
complies with general-purpose exterior requirements.
All wiring is to a Breaker Box provided on
the side of the Building. A building grounding
system is provided along with internal grounding
attachments. |
| |
| MINIMUM
SPECIFICATIONS |
- FIRE
DOOR(s): 3 hr. labels, (WxH) 5' x 6'8";
double door assembly; w/automatic door
closure, keyed lock assembly, door sweep,
easily adjustable and replaceable (not
welded in place), and commercially available.
- RAIN
SHIELD: Rain shield installed above each
door.
- SUMP:
Minimum 6" Deep sump fabricated from
welded heavy gauge A569 steel; all seams
welded liquid tight; all floor supports
and the raised floor must be easily removable
and not permanently attached.
|
|
CORROSION PROTECTION: |
- Exterior
subfloor finish - Exterior commercial
grade elastomeric finish on the entire
subfloor.
- Interior
finish - Immersion grade 2 part epoxy;
white.
- Exterior
finish - Prime coat immersion grade 2
part epoxy; top coat 2 part polyurethane;
gloss white.
|
| VENTILATION: |
|
Passive cross floor ventilation except where
electro-mechanical ventilation is specified. |
| AIR
VENTS: |
- Exterior
Covering - Galvanized rain shield with
bug screen.
- Interior
Covering - Louvered cover. (Adjustable
on buildings with heating or air conditioning.)
- Fire
Damper - Installed in Fire-rated buildings;
curtain type UL listed and approved for
use in 2 hour fire-rated buildings, 1.5
hour rated; for use in 4 hour fire-rated
buildings, 3 hour rated.
|
| SIGNS: |
| Building
must have a minimum of the following signs: |
- One
approved DOT placard and 704M label for
each door opening;
- Approval
label of 3rd party nationally recognized
testing laboratory;
- Manufacturers
name and telephone number;
- Label
each appliance and control switch.
- Label
all circuit breakers.
|
| INTERIOR
GROUNDING: |
| Each
compartment must have interior grounding connections. |
|
BUILDING GROUND: |
| The
building must be supplied with a minimum eight
foot grounding rod and connections and wire. |
| SEISMIC
BRACING: |
|
The
building must be supplied with seismic tie
down brackets, which meets or surpasses
code requirements for seismic Zone 4.
|
| OPERATION
MANUAL: |
|
The building must arrive with a manual detailing
the operation of the building and each piece
of equipment, including diagrams and drawings;
maintenance schedule; cut sheets for all
finishes and equipment provided; maintenance
manuals for all equipment including fire
suppression system(s), heating and air conditioning
equipment; a drawing showing an overview
of the building and all its requisite equipment;
a drawing showing the structural section
of the building; a schematic of the electrical
equipment installed; and complete Warranty
Statement.
|
|
TOUCH UP PAINT: |
| The
building must arrive with touch up paint for
the interior finish and for the exterior finish. |
|
WARRANTY:
1 Year std. w/10 years on structural
Limited Warranty; a complete Warranty Statement
is provided.
|
| |
|
|
| Note
(1): Dimensions, capacities and weights are
nominal and will vary with Optional Features
required. Note (2): Double stacking is not
allowed with Class 1a and 1b flammable liquids,
and certain other hazardous materials; consult
with the "authority having jurisdiction."
|